Fronius inverter state codes: Primo, Symo and GEN24, explained
As at November 2026, Fronius Primo and Symo inverters show three-digit state codes: 102 to 108 are grid faults, 3xx short interruptions such as heat, 4xx hardware and 5xx warnings. GEN24 models use four-digit codes such as 1114. Most red lights after a storm or on a hot afternoon are grid or temperature faults that clear themselves. Here is how to tell.
Written by Juan Flinn, Content Editor · Reviewed by the Mission Green Energy Team · Updated 9 November 2026
Which Fronius do you have,
and where is the code?
The two families number their codes differently, so this matters first.
The Primo (3.0–8.2 kW single-phase) and Symo (three-phase) are the older SnapINverter range with a screen and buttons. The code shows on the screen, and the red general status LED lights while a status message is displayed. Orange means it is starting up, self-testing or updating; green means it is feeding power in.
The Primo GEN24 and Symo GEN24 have no code screen. Their codes appear in the inverter’s web interface (System > Event Log, or Notifications) and in Fronius Solar.web. What each GEN24 light means is on our inverter red light guide. Other brands: Sungrow fault codes and GoodWe error codes.
Fronius makes one point in both SnapINverter manuals that saves a lot of worry: a status code can appear briefly as part of the inverter’s normal control response. If it then keeps working, there was no fault.
102–108 · 1114 · 1119
Grid voltage, frequency or outage. Fronius’s own example says there is nothing wrong with the device.
306 · 307
Not enough sun to feed in yet. The manuals say these don’t indicate any kind of fault.
475 · 1082 · 1173 · 1030
Earth and insulation faults, repeated arcs and a tripped surge protector. Call your installer.
Which Fronius code
is on your screen?
Primo and Symo codes from their operating instructions (editions 030-15102024 and 044-17072025); GEN24 codes from the Primo GEN24 operating instructions (043-01092026) and the GEN24, Tauro and Verto country setup manual (017-10072026). The plain-English wording is ours.
| Primo / Symo | GEN24 | Fronius’s description | What you can safely do |
|---|---|---|---|
| 102 | 1114 | AC voltage too high | Wait: it reconnects once the grid is back in range. If it keeps recurring, call your installer. |
| 103 | 1119 | AC voltage too low | Wait. If it keeps recurring, call your installer. |
| 105 / 106 | 1035 / 1037 | AC frequency too high / too low | Wait. If it keeps recurring, call your installer. |
| 107 | — | No AC grid | Check whether the house and street have power. If the house does, call your installer. |
| 108 | 1004 | Stand-alone operation detected / Islanding detected | The grid dropped out. Wait for it to return. |
| — | 1115, 1116 | Grid voltage too high (fast overvoltage cut-out, above 135%) | Wait. If it repeats, call your installer. |
| — | 1117 | Long-term mains voltage limit exceeded | Grid voltage averaged too high. If it repeats on sunny afternoons, call your installer. |
| 112 | — | RCMU error (residual current monitoring) | If it keeps recurring, call your installer. |
| 303 / 304 | — | Overtemperature (power stage set and internal on Primo; DC and AC module on Symo) | Clears as it cools. Keep the vents clear. If it recurs, call your installer. |
| 306 / 307 | — | PV output too low / DC voltage too low | Normal at dawn and dusk. Only a problem in full sun. |
| 326 / 327 (Symo) | — | Fan 1 / Fan 2 error | Call your installer. |
| 431 | — | Software problem | The manual’s step is an AC reset (circuit breaker off and on). If it stays, call. |
| 447 | — | Insulation fault | If it keeps recurring, call your installer. |
| 475 | — | Solar module ground, insulation fault | Not feeding in. Don’t touch anything. Call your installer. |
| 457 | — | Grid relay sticking | Not feeding in. Needs a Fronius-trained technician. |
| 502 | 1083 / 1082 | Insulation error on the solar modules / isolation warning / isolation error | A warning (502, 1083) or a stop (1082). If it keeps recurring, call an electrician. |
| 509 | — | No energy fed into the grid in the past 24 hours | Acknowledge it, then look for another code that explains why. |
| 516 | — | No communication possible with the storage unit | Call your installer if it stays. |
| 517 | — | Power derating caused by too high a temperature | Clears as it cools. If it recurs, call your installer. |
| 566 | — | Arc detector switched off | Not an error. It shows daily until the arc detector is switched back on. |
| — | 1006 | ArcDetected (yellow flashing) | The manual says it restarts by itself after 5 minutes. Note it. |
| — | 1173 | ArcContinuousFault (red flashing) | Don’t clear it. Call your installer to check the system first. |
| — | 1030 | WSD Open (red flashing) | Often a tripped surge protector, which must be repaired by an authorised specialist. |
Fronius’s customer-service note is simple: contact your Fronius dealer or a Fronius-trained technician if an error appears often, all the time, or isn’t in the tables. If your code isn’t here, we couldn’t confirm it in a current Fronius document for these models.
Why does a Fronius show 102 or 1114
after a storm or on a sunny afternoon?
Class 1 codes are the grid’s problem, and Fronius says so.
The Primo and Symo manuals describe class 1 codes as generally momentary and caused by the public grid. Their example is a grid frequency that is too high, and the line that follows is plain: there is nothing wrong with the device. The inverter disconnects, watches the grid for a set period, then reconnects and ramps its output back up.
After a storm, expect 107 (No AC grid), 103 or 108 on a SnapINverter, and 1119 or 1004 on a GEN24. The GEN24 waits a set “reconnection” time before switching back on, which the country setup allows from 1 to 900 seconds. So a few minutes of nothing after the power returns is normal.
On a sunny afternoon, expect 102 or 1114, and on a GEN24 also 1117, the long-term voltage average. That is the street’s solar pushing local voltage up. Fronius’s remedy for a recurring 102 is to check the grid connections and call your installer, who can measure the voltage and take it up with the network. Our guide to solar that has stopped exporting covers the voltage problem.
Why does a Fronius show 306 or 307
at sunrise?
Two codes that look alarming and aren’t.
306 (PV output too low) and 307 (DC voltage too low) mean the panels aren’t producing enough to feed in yet. Both SnapINverter manuals say they appear routinely early in the morning and in the evening and don’t indicate any kind of fault. They only matter if they show in full sun, which points to a panel or wiring problem for your installer.
509 means no energy was fed in for 24 hours. The manual says to acknowledge it and check the conditions for feeding in; its example is panels covered in snow. In most of Australia, look instead for a second code that explains the stop. 566 (arc detector switched off) is not an error either: it repeats daily until the detector is switched back on. Unsure whether the system is producing at all? Try our sixty-second solar check.
What do 447, 475, 502
and GEN24’s 1082 and 1083 mean?
Water, damaged cable, and how to tell weather from a fault.
All of these mean the inverter has found a path between the solar wiring and earth. The GEN24 measures insulation at its DC terminals before every connection, at least once a day. If the reading drops below a warning limit it shows 1083 as a warning; below the error limit it shows 1082 and refuses to feed in. The technical data in the Primo GEN24 manual gives the warning and shutdown threshold as below 100 kΩ.
On a SnapINverter, 502 is a warning that stays on the screen until acknowledged, 447 is an insulation fault, and 475 (solar module ground, insulation fault) stops it feeding in. For every one, Fronius’s remedy is the same: if it keeps recurring, contact your installer.
A single warning on a wet morning that never returns is moisture. A code that returns after rain, or appears in dry weather, means water is getting into a connector or a cable is damaged, and only an electrician with test gear can find it.
Why does a Fronius slow down
or stop on hot afternoons?
Derating first, then a short stop.
As it heats up, a SnapINverter first cuts its output and shows 517 (power derating caused by too high a temperature). If it gets hotter, it stops briefly with 303 or 304 and restarts by itself as it cools. The Symo adds 325 for heat in the connection area and 326 and 327 for fan errors.
Fronius’s remedy is to clear the cooling-air openings and heat sink if needed. The part you can do is keep the vents unobstructed. Cleaning the heat sink and fan means opening the unit on a GEN24 and using compressed air on the fan: that is installer work. If the codes come back every summer, ask your installer about shade and airflow.
What do GEN24 codes 1006, 1173
and 1030 mean?
The three GEN24 codes in the operating instructions, and the one to leave alone.
1006 ArcDetected means the inverter detected an electric arc in the solar wiring and stopped. The manual says no action is required: it starts feeding in again after 5 minutes. 1173 ArcContinuousFault means it has reached its maximum number of automatic reconnections in 24 hours. The manual lets the code be confirmed by holding the light sensor for 3 seconds, but first says the entire solar system must be checked for damage, and damaged parts repaired by qualified specialists. So don’t hold the sensor to clear 1173; call your installer.
1030 WSD Open means the wired-shutdown safety chain is open. The first cause the manual gives is a tripped surge protection device, in which case the inverter must be repaired by an authorised specialist.
One trap if you have an older Symo manual in the drawer: it says codes 1000 to 1299 are internal processor information, of no concern when the inverter works. On a GEN24 the 1000s are the real fault codes. Check which manual matches your model.
How do I safely restart
a Fronius inverter?
Breaker off, DC off; DC on, breaker on.
Don’t restart for 475, 1082, 1173 or 1030, or if there is a smell, smoke, scorching or damage. For the rest, Fronius gives the same order for every model:
- Turn off the inverter’s circuit breaker at the switchboard.
- Turn the DC disconnector on the inverter to OFF.
- Wait. The GEN24 manual says 2 minutes for the capacitors to discharge; the Primo and Symo manuals say 5 minutes before the unit is opened. Waiting 5 covers both.
- Turn the DC disconnector back ON first.
- Turn the circuit breaker back on last.
That is the opposite order to some other brands, which switch the AC on first, so follow your own manual. On a GEN24 with a battery, the battery has its own sequence: with a BYD Battery-Box Premium, the manual says switch the battery on before the breaker and DC disconnector. After a full system shutdown, the GEN24 restarts by itself when energy returns, but the battery must be started by hand. For codes 431 and 482, Fronius’s own fix is an “AC reset”: the circuit breaker off and on again. If the code comes straight back, stop and call.
Is a Fronius fault
covered by warranty?
Fronius Australia’s warranty page, read 9 November 2026.
Fronius Australia offers a free 10-year Warranty Plus if the inverter is registered on Solar.web within 30 months of delivery. Cover starts at commissioning, includes materials, servicing and transport costs, and can be extended to 15 years for a fee bought within 6 months of the warranty starting. Inverters installed before 1 October 2024 may instead qualify for the older 5+5 offer, which needed registration within 24 months of installation and covers parts.
If you have never logged in to Solar.web, check now whether your inverter is registered: it decides whether you have 10 years or much less. Start any claim with your installer or a Fronius-trained technician, with the code and a photo. If the installer has gone, see how to claim when the installer is gone.
When should you stop
and call an electrician?
Any one of these is enough.
- Smoke, a burning smell, scorch marks, melted plastic, or a buzzing switch.
- Codes 475, 1082, 1173 or 1030.
- An insulation code (447, 502, 1083) that keeps coming back.
- The same grid code most sunny afternoons, or 107 while the house has power.
- 306 or 307 in full sun, or a fan code on a Symo.
- Any code shown all the time, or one not in the tables.
If the faults are piling up on an older SnapINverter, read when an inverter needs replacing. More on the brand is on our Fronius page, and on repair and battery retrofits in Adelaide and Brisbane.
Fronius state codes:
your questions, answered.
Code 102 is AC voltage too high: the grid voltage at your home went above the inverter's limit, so it disconnected. Fronius's Primo and Symo manuals (2024 and 2025 editions) class it as a grid code that is generally momentary, and say the inverter resumes once the grid is back in range. GEN24 models show the same fault as 1114. If it keeps recurring, often on sunny afternoons, call your installer to measure the voltage.
Code 107 is No AC grid: the inverter can't see a grid supply, usually because of a blackout or because its own circuit breaker is off. Fronius's Primo operating instructions (edition 030-15102024) say it reconnects after checking that the grid is back within the permitted range. If your house has power and 107 stays, the inverter's breaker may have tripped; call your installer rather than resetting it repeatedly.
Codes 306 (PV output too low) and 307 (DC voltage too low) mean the panels aren't yet producing enough power to feed into the grid. Fronius's Primo and Symo manuals (2024 and 2025 editions) say both appear routinely early in the morning and in the evening and don't indicate any kind of fault. They only matter if they appear in full sun, which points to a panel or wiring problem for your installer.
Both are insulation warnings: the inverter has measured a weak path between the solar wiring and earth. 502 is the Primo and Symo code; 1083 is the GEN24 warning, and 1082 the GEN24 error that stops feed-in. Fronius's July 2026 GEN24 country setup manual says the inverter measures insulation before every connection, at least daily. One warning on a wet morning may be moisture; if it recurs, call an electrician.
1173 ArcContinuousFault means the GEN24 has detected electric arcs in the solar wiring and reached its maximum number of automatic reconnections in 24 hours, so it has stopped. The Primo GEN24 manual (edition 043-01092026) allows the code to be confirmed by holding the sensor for 3 seconds, but only after the whole solar system has been checked for damage. Don't clear it yourself: call your installer.
Fronius gives the same order for Primo, Symo and GEN24: switch the inverter's circuit breaker off, turn the DC disconnector off, wait (2 minutes on a GEN24, per its 2026 manual), then turn the DC disconnector on first and the breaker on last. Don't do it for codes 475, 1082, 1173 or 1030, or if there is smoke or a burning smell. If the code returns, call your installer.
Fronius Australia's warranty page, read November 2026, offers a free 10-year Warranty Plus if the inverter is registered on Solar.web within 30 months of delivery. Cover starts at commissioning and includes materials, servicing and transport costs, and can be extended to 15 years for a fee within 6 months. Inverters installed before 1 October 2024 may fall under the older 5+5 offer instead.
Where these
figures come from.
Every code, description and step above comes from Fronius’s own operating instructions and its Australian warranty page, read 9 November 2026. The plain-English summaries are ours. This is general information: your installer and your model’s manual come first.
- Fronius — Primo 3.0-1 to 8.2-1 operating instructions, edition 030-15102024
- Fronius — Symo / Eco operating instructions, edition 044-17072025
- Fronius — Primo GEN24 3–6 kW operating instructions, edition 043-01092026
- Fronius — GEN24, Tauro and Verto country setup menu operating instructions, edition 017-10072026
- Fronius Australia — Warranty models